Cable Voltage Drop Calculator - Minimum Cable Size

Estimate voltage drop over a cable run from load current, length, conductor material, and size — plus whether it stays within acceptable limits.

Enter measurements

Result

Enter measurements to calculate a result.

Formula

Voltage drop = √3 × I × (k × L ÷ CSA) for three-phase; I × (k × L ÷ CSA) for single-phase. k = 0.0175 (copper), 0.028 (aluminium) Ω·mm²/m.

Worked examples

230 V, 16 A, 25 m, 2.5 mm² copper, single-phase

≈ 2.8 V drop (1.2%) — within 3%.

400 V, 32 A, 50 m, 6 mm² copper, three-phase

≈ 4.9 V drop (1.2%) — acceptable.

Questions and assumptions

Why does material matter?

Copper has lower resistivity than aluminium, so for the same size it drops less voltage.

Is 3% the right limit?

3% is a common rule of thumb for branch circuits; 5% is often the absolute maximum. Check your local electrical code.