Cable Voltage Drop Calculator - Minimum Cable Size
Estimate voltage drop over a cable run from load current, length, conductor material, and size — plus whether it stays within acceptable limits.
Result
Enter measurements to calculate a result.
Formula
Voltage drop = √3 × I × (k × L ÷ CSA) for three-phase; I × (k × L ÷ CSA) for single-phase. k = 0.0175 (copper), 0.028 (aluminium) Ω·mm²/m.
Worked examples
230 V, 16 A, 25 m, 2.5 mm² copper, single-phase
≈ 2.8 V drop (1.2%) — within 3%.
400 V, 32 A, 50 m, 6 mm² copper, three-phase
≈ 4.9 V drop (1.2%) — acceptable.
Questions and assumptions
Why does material matter?
Copper has lower resistivity than aluminium, so for the same size it drops less voltage.
Is 3% the right limit?
3% is a common rule of thumb for branch circuits; 5% is often the absolute maximum. Check your local electrical code.